Langelier Saturation Index

LSI Calculator

Set the cycled water, then read the equilibrium verdict at the pipe wall. Supporting factors and the temperature curve wait until the current chemistry is established.

Model 04 · Open to everyone

Operating case

Set the water

Makeup chemistry, cycles, and heat establish the pipe verdict.

100ppm

What the scale is made of. Cycles multiply it into factor C.

100ppm

Drives both the estimated pH and factor D.

5.0

The multiplier on the whole analysis.

90°F

Hot surfaces scale first.

Analysis detailDissolved solids
300ppm

Factor A, the smallest lever of the four.

Operating verdictScale forming+2.02 LSI at the wall
Concentration5.0×1,500 ppm cycled TDS
Surface temperature90 °FPipe consequence responds
Live saturation verdictScale forming
Langelier saturation index, liveTHE BLUEPRINT OF WATER · SATURATION INDICES−3−2−10+1+2+3CORROSIVEBALANCEDSCALE FORMINGSCALE FORMINGMAKEUP ANALYSISCa100 ppmM alk100 ppmTDS300 ppm× 5.090 °F recirculatingTHE PIPE WALL ANSWERS90 °F · scale forming
Diagram controlsInspect a live quantity
Live relationship

Current equation

Supporting readoutsSeven measurementsOpen
Cycled calcium500ppm
Cycled alkalinity500ppm
VerdictScale forming±0.3 display bands
Operating curveLangelier index versus temperature90 °F selected

LSI vs temperature

Drag the plot to set the water temperature. The hottest surface in the loop sits to the right of the bulk reading.

0+1+26080100120140WATER TEMPERATURE °FBALANCE90 °F, +2.02
Reference

How the saturation index model works

The Langelier Saturation Index compares the water's operating pH with the pH at which it would be exactly saturated with calcium carbonate. Positive means the water tends to scale, negative means it tends to corrode. In a cooling tower the water that touches the pipe wall is the cycled water, not the makeup, so the analysis is concentrated first.

The instrument above runs the chemistry live. The governing relationships are written out below.

The formulas follow Chapter 8 of the book, Scale.

The cycled analysis

Cycled analysis=Makeup analysis×Cycles\text{Cycled analysis} = \text{Makeup analysis} \times \text{Cycles}

Cooling tower water concentrates as it cycles. Each makeup analysis (calcium, alkalinity, TDS) is multiplied by the cycles of concentration to get the value the recirculating water actually sees.

Makeup analysis
Makeup calcium, M alkalinity, or TDS (each as CaCO3 where applicable) (ppm)
Cycles
Cycles of concentration
Assumes
  • Conservative concentration: every analysis scales linearly with cycles.

Saturation pH

pHs=(9.3+A+B)(C+D)\text{pH}_s = (9.3 + A + B) - (C + D)

The saturation pH: the pH at which the cycled water is exactly in balance with calcium carbonate. A = (log₁₀ TDS − 1) / 10, B = −13.12 × log₁₀(°C + 273) + 34.55, C = log₁₀(Ca) − 0.4, D = log₁₀(M alk).

TDS
Cycled total dissolved solids (sets A) (ppm)
Temperature
Recirculating temperature (sets B) (°F)
Ca as CaCO₃
Cycled calcium hardness (sets C) (ppm)
M alk as CaCO₃
Cycled M alkalinity (sets D) (ppm)
Assumes
  • Calcium carbonate saturation reference.
  • Temperature converted to °C internally.

Langelier Saturation Index

LSI=pHpHs\text{LSI} = \text{pH} - \text{pH}_s

The Langelier Saturation Index. Positive means the water tends to scale, negative means it tends to corrode, and most programs aim for roughly 0 to +1.

pH
Recirculating pH (measured or Caplan estimate)
pHs
Saturation pH
Assumes
  • Index only; not a rate.

Ryznar Stability Index

RSI=2×pHspH\text{RSI} = 2 \times \text{pH}_s - \text{pH}

The Ryznar Stability Index, a less sign-sensitive companion to LSI. Under 6 scales, 6 to 7 is roughly stable, and over 7 turns corrosive.

pHs
Saturation pH
pH
Recirculating pH
Assumes
  • Index only; reported without PSI.

Worked example

Take the room's default case: makeup at 100 ppm calcium, 100 ppm alkalinity, and 300 ppm TDS, run at 5 cycles and 90°F.

Cycled calcium
500 ppm
Cycled alkalinity
500 ppm
Cycled TDS
1,500 ppm
Estimated pH
8.49
Saturation pH
6.47
LSI
+2.02
RSI
4.45

Read the index against the bands: positive tends to scale, negative tends to corrode, and most programs aim for roughly 0 to +1.

Common questions

What does a positive LSI mean?
Positive means the water tends to deposit calcium carbonate scale, and negative means it tends to dissolve it and corrode. The index states a tendency, not a rate; most programs aim for roughly 0 to +1.
Why is the makeup analysis cycled first?
The recirculating water, not the makeup, touches the heat exchange surfaces. Each analysis value is multiplied by the cycles of concentration so the index describes the water the pipe wall actually sees.
How do LSI and RSI differ?
Both compare the operating pH with the saturation pH. LSI is pH minus saturation pH. RSI is twice the saturation pH minus the operating pH, read on its own bands: under 6 scales, 6 to 7 is roughly stable, and over 7 turns corrosive.