≈ 43 to 45 gpm (ceiling)
Static-reading mode, a ceiling. The supply will sag under flow. Range spans nominal C to C × 0.85.
Of 75.0 psi available at 45 gpm, 75.0 psi is spent getting water to the destination.
This is the 200-vs-100 lesson with names on it. The miss is never the math, it is the inventory.
This flow exceeds the softener’s design service rate: 45 gpm through a vessel rated 31.4 gpm. Expect elevated ΔP and hardness leakage late in the run. Size the softener →
Sites, systems, and saved comparisons arrive with accounts. The result stays on screen either way.
Sources & assumptions: Hazen-Williams with Sch40 IDs (ASME B36.10). C-factors per standard references, range = nominal to C × 0.85. Backflow curves typical of RP/DC assemblies (Watts, Febco, Zurn Wilkins; verify one curve per type and cite). Valve Cv typical of manufacturer catalogs (Fisher/Emerson, Cla-Val, ASCO; actual ±40% by trim, enter the submittal Cv when you have it). Strainer and meter per typical clean-strainer and AWWA C700/C701 allowances (a dirty strainer loses 3 to 5 times this, one more reason to measure). Softener ΔP = rated × (Q/Qᵣ)¹·⁸. The calculator estimates; the field measures.